Home  | Sitemap | Contact Us |中文
 
Company Profile
Successful Cases
Contact Us
Technical Information
en

SL1900H-ST Humidifier controller

 

Adopt advanced fuzzy algorithm, stable, precision up to ±2%, linear error via current detection<0.1%, proportion drainage/influent control, improve the humidified efficiency, adapt to different kinds of cylinder and water quality. Suitable for high-precision electrode humidifier control

 

Electrode Humidifier of Constant Temperature and Humidity units.

line
 

*Compose integrated humidifier control system together with a upper controller.
*Digital or analogue control, 0~10V or 0~5V proportion analogue value control input;
*Current transducer input 0~40A;
*Suitable for 2~46Kg/h three-pole or six-pole electrode humidifier;
*Proportion water drainage/influent control, accurately control the humidity;
*Support setting water drainage time and draining interval;
*High current alarm, zero current alarm, electrode fault protection, water leakage protection, soft water quality remind, low current protection;
*SMT technology, 48 hrs burn-in test for ensuring quality;
*PCB Surface painted with CRC, avoid leakage, short circuit, and erosion from acid/ alkali/ alcohol/ humidity/salt spray;
*Wide voltage range, avoid misoperation caused by voltage fluctuation;
*All I/O on control board fixed with indicator lights for intuitionistic estimation. Implement control logic on the control board;
*Featured with European terminal blocks for I/O connection, easy assembly;
*Support secondary water influent, auto cleaning timer, high humidification efficiency;
*Stable voltage 5V control all input and output points, avoid misoperation caused by voltage fluctuation;
*support External manual drain switch.

 

Voltage range of potentiometer, digital or analogue value option, external analogue value range, number of electrode, weight of humidity (Kg), cleaning interval, cleaning time, humidity control.

 

*Controller dimension: 154mm×110.5mm(Including terminal blocks), fixed by 4 fixing holes (Hole dia:4.5mm),   transverse hole distance 118mm, vertical hole distance 98mm;
*2 digital inputs: High water level, Remote control;
*5 relay outputs: Humidifier electrode contactor , Water drainage valve, Water influent valve, Fault outputs, Manual   drainage;
*2 analogue inputs: 0~10V control signal, Current transformer signal;
*Relay power output: 250V/5A;
*3 digit LED and 7 status indicator

 
 
COPYRIGHT©SYSLAB     ALL RIGHTS RESERVED 粤ICP备07001651
Rm.5, 3/F, University-town Business Park, Lishan Road, Taoyuan Str., Nanshan, Shenzhen, China 518055
Tel: +86-755-26611785    Fax: +86-755-26617755