*Four control modes for humidifier, integrate humidifier precision control.
*Build-in phase protection function.
*Intelligence control of the temperature and humidity to achieve a balance environment.
*Advance fuzzy algorithms, more accurate and stable to detect the current. The precision can reach to±2%,the mistake rate will less the 0.1%.
*Up to 6 units control, duty standby function, in order to enhance the stability.
*Suitable for different units: Air-cooled, Water cooled, selectabled on the controller board via dial switch.
*Max /Min temp.and humidity can be set easily, flexible used, suitable for different environment.
*Water coil cooling and compressor cooling selectable.
*Suitable for 2-46Kg/h three-pole or six-pole cylinder, proportional inlet and outlet water. High precision control.
*Drain time settable. Timer clean function.
*High water level alarm, Soft water quality alarm, low current alarm.
*Control heating by 0-10V SCR, Support 0-10V VFD control.
*Support auto restart function, support terminal chain control.
*Trial run function; Memory function; Supply air temperature high, low protection; Probe fault protection.
*Strong stability, 0.15-80MHz interference rejection, 4KV high voltage and surge resistance
*SMT technology, 48 hrs burn-in test for ensuring quality
*MODBUS-RTU RS485 Widely-used communication protocol, up to 1km max distance (Gateway Free);
*PCB Surface painted with CRC, avoid leakage, short circuit, and erosion from acid/ alkali/ alcohol/ humidity/salt spray;
*Featured with tension and torsion resistance probe, long working life
*Wide voltage range, avoid misoperation caused by voltage fluctuation
*Control logic implemented on the control board. Continue working even HMI has fault.
|
| |
Temp. setting, Humidity setting, Temperature amendation,
Humidity amendation, Manual drain, Auto restart,
Timer ON/OFF, Running time setting, PL delay,
Compr. min running time, Compr. min stop time, Compressor start delay,
Common alarm dalay, Max cooling (stage 1), Min cooling (stage 1),
Max cooling (stage 2), Min cooling (stage 2), Max heating (stage 1),
Min heating (stage 1), Max heating (stage 2), Min heating (stage 2),
Max humidify, Min humidify, Max dehumidify,
Min dehumidify, Condenser fan start temp (cooling), High supply temp, Low supply temp, Supply air temp diff., Number of compressors,
Number of E-heaters, VFD low speed, Heating mode,
The second analogue output setting, Use VFD or not Working mode,
Standby function, No. of standby unit, Address of standby unit,
Duty time setting, Temp. diff. alarm, Humidify pole selectable,
Humidifier mode selectable, Humidifier capacity selectable, Second inlet water time,
Ratio of drain, Drain time setting, Drain interval,
Input NO/NC
|